Sita 412 LCD PLUS: 40W UV Disinfection System with Lamp Countdown (45 l/min)

The Sita 412 LCD PLUS is part of SITA's LCD commercial-grade UV range, manufactured in Italy to ISO 9001 quality standards and WRAS approved. Like every Sita LCD system, it uses a 304 stainless steel chamber (316 optional) and disinfects water by exposing it to UV-C light as it passes through, inactivating bacteria and viruses without any chemicals or additives.

The PLUS control adds a UV intensity meter (or temperature meter), a resettable countdown hour meter with an end-of-lamp-life alarm, on-screen irradiation/temperature display, and automatic shutdown if the chamber overheats — on top of the standard LCD display, hours-run meter, fault light and alarm relay contact.

Specifications

Lamp rating 40W
Flow rate 45 l/min
Connection 1in male
Chamber 304 stainless steel (316 optional), 925mm length
Lamp life 9,000 hours
Control LCD PLUS: UV intensity/temperature meter, resettable lamp countdown with alarm, high-temperature shutdown, 4-20mA output
Electrical supply 230V, 50/60Hz, IP55
Operating temperature 2–40°C
Max pressure 9 bar

Who it's for

  • Commercial and industrial premises wanting live UV intensity monitoring, not just a lamp-failure alarm
  • Sites where high-temperature protection for the chamber matters
  • Anyone who'd rather see a lamp-life countdown than guess at an annual change date

Why it matters

UV systems should be sized generously against your actual site flow rate — as a rule of thumb, the UV's rated flow should be at least 4 times your required or achievable flow, or you should restrict flow to no more than 38% of the system's maximum rating. We'd also recommend physical pre-filtration ahead of the UV rather than relying on the UV alone: a triple-filter setup (5 micron string wound, 1 micron polyspun, then a 0.45 micron absolute filter) is a common specification, with two absolute filters in parallel where higher flow is needed.

Have You Ordered Before?

Existing/previous customers can find their previous orders with just a surname and a postcode. There’s no better way to find parts and replacements!

Get Started
Pallas (Sita) 412 LCD PLUS 1 x 40w - 45Lpm - 2.7m3/hr 1" connection

Pallas (Sita) 412 LCD PLUS 1 x 40w - 45Lpm - 2.7m3/hr 1" connection

Regular price £1,220.00 inc. VAT
£1,016.67 ex. VAT
Sale price £1,220.00 inc. VAT
£1,016.67 ex. VAT

Frequently asked questions

For full details on returns, refunds, eligibility, and timeframes, please refer to our complete Refund Policy here:

👉 Refund and Returns Policy

If you are unsure whether your item qualifies for return, please contact our team before sending anything back and we’ll be happy to help.

A UV intensity meter (or temperature meter), a resettable countdown hour meter with an end-of-lamp-life alarm, on-screen irradiation/temperature display, and automatic shutdown if the chamber overheats.

Yes — it shuts down automatically if the UV chamber reaches a high temperature, a feature the standard LCD control doesn't include.