Sita 440 LCD: 40W UV Disinfection System (60 l/min)

The Sita 440 LCD is part of SITA's LCD commercial-grade UV range, manufactured in Italy to ISO 9001 quality standards and WRAS approved. Like every Sita LCD system, it uses a 304 stainless steel chamber (316 optional) and disinfects water by exposing it to UV-C light as it passes through, inactivating bacteria and viruses without any chemicals or additives.

The LCD control panel gives you an LCD display, an hours-run meter, a red LED fault light, a free alarm relay contact (NO/NC, 2A max), a 4-20mA output, and an O-Norm/DVGW approved sensor — useful if you want to tie the system into a building management system. If you'd also like a UV intensity meter, a resettable lamp-life countdown, and automatic high-temperature shutdown, the LCD PLUS version of this model adds those.

Specifications

Lamp rating 40W
Flow rate 60 l/min
Connection 1.5in male
Chamber 304 stainless steel (316 optional), 880mm length
Lamp life 9,000 hours
Control LCD display, hours-run meter, red LED fault light, alarm relay (NO/NC, 2A max), 4-20mA output
Electrical supply 230V, 50/60Hz, IP55
Operating temperature 2–40°C
Max pressure 9 bar

Who it's for

  • Commercial and small industrial premises wanting BMS-ready monitoring via the alarm relay and 4-20mA output
  • Sites on 1.5in pipework needing 60 l/min UV disinfection
  • Anyone who wants a proper control panel rather than a basic LED indicator

Why it matters

UV systems should be sized generously against your actual site flow rate — as a rule of thumb, the UV's rated flow should be at least 4 times your required or achievable flow, or you should restrict flow to no more than 38% of the system's maximum rating. We'd also recommend physical pre-filtration ahead of the UV rather than relying on the UV alone: a triple-filter setup (5 micron string wound, 1 micron polyspun, then a 0.45 micron absolute filter) is a common specification, with two absolute filters in parallel where higher flow is needed.

Have You Ordered Before?

Existing/previous customers can find their previous orders with just a surname and a postcode. There’s no better way to find parts and replacements!

Get Started
Pallas (Sita) 440 LCD 1 x 40w - 60 Lpm - 3.6m3/hr 1.5" connection

Pallas (Sita) 440 LCD 1 x 40w - 60 Lpm - 3.6m3/hr 1.5" connection

Regular price £1,075.00 inc. VAT
£895.83 ex. VAT
Sale price £1,075.00 inc. VAT
£895.83 ex. VAT

Frequently asked questions

For full details on returns, refunds, eligibility, and timeframes, please refer to our complete Refund Policy here:

👉 Refund and Returns Policy

If you are unsure whether your item qualifies for return, please contact our team before sending anything back and we’ll be happy to help.

LCD models give you an LCD display, hours-run meter, red LED fault light and alarm relay contact. LCD PLUS adds a UV intensity/temperature meter, a resettable lamp-life countdown with alarm, and automatic shutdown if the chamber overheats.

Yes — it has a free alarm relay contact (NO/NC, 2A max) and a 4-20mA output for tying into a BMS.