Skip to product information
1 of 1

Pallas (Sita) 550 LCD 2 x 40w - 100 lpm - 6.0m3/hr 1.5" connection

Pallas (Sita) 550 LCD 2 x 40w - 100 lpm - 6.0m3/hr 1.5" connection

SKU:550-LCD

Regular price £1,470.00 inc. VAT
£1,225.00 ex. VAT
Sale price £1,470.00 inc. VAT
£1,225.00 ex. VAT
Shipping calculated at checkout.
Shipping is calculated at checkout
tick in circle

All our orders are sent with tracked courier services

tick in circle

Free Customer Support by experts

Product Description

Sita 550 LCD: Twin-Lamp UV Disinfection System, 2 x 40W (100 l/min)

The Sita 550 LCD is the largest twin-lamp model in SITA's LCD commercial-grade UV range, manufactured in Italy to ISO 9001 quality standards and WRAS approved. Two 40W lamps in a single 304 stainless steel chamber (316 optional) give it the highest flow rate of the standard single-chamber LCD models before stepping up to the multi-lamp RACK series.

The LCD control panel gives you an LCD display, an hours-run meter, a red LED fault light, a free alarm relay contact (NO/NC, 2A max), a 4-20mA output, and an O-Norm/DVGW approved sensor — useful if you want to tie the system into a building management system. If you'd also like a UV intensity meter, a resettable lamp-life countdown, and automatic high-temperature shutdown, the LCD PLUS version of this model adds those.

Specifications

Lamp configuration 2 x 40W (80W total)
Flow rate 100 l/min
Connection 1.5in male
Chamber 304 stainless steel (316 optional), 985mm length
Lamp life 9,000 hours
Control LCD display, hours-run meter, red LED fault light, alarm relay (NO/NC, 2A max), 4-20mA output
Electrical supply 230V, 50/60Hz, IP55
Operating temperature 2–40°C
Max pressure 9 bar

Who it's for

  • Commercial premises needing the highest flow rate available from a single-chamber LCD system
  • Sites wanting BMS-ready monitoring via the alarm relay and 4-20mA output
  • Applications approaching RACK-series territory but not yet needing multiple lamps in separate chambers

Why it matters

UV systems should be sized generously against your actual site flow rate — as a rule of thumb, the UV's rated flow should be at least 4 times your required or achievable flow, or you should restrict flow to no more than 38% of the system's maximum rating. We'd also recommend physical pre-filtration ahead of the UV rather than relying on the UV alone: a triple-filter setup (5 micron string wound, 1 micron polyspun, then a 0.45 micron absolute filter) is a common specification, with two absolute filters in parallel where higher flow is needed.

Have You Ordered Before?

Existing/previous customers can find their previous orders with just a surname and a postcode. There’s no better way to find parts and replacements!

Get Started
Pallas (Sita) 550 LCD 2 x 40w - 100 lpm - 6.0m3/hr 1.5" connection

Pallas (Sita) 550 LCD 2 x 40w - 100 lpm - 6.0m3/hr 1.5" connection

Regular price £1,470.00 inc. VAT
£1,225.00 ex. VAT
Sale price £1,470.00 inc. VAT
£1,225.00 ex. VAT

Frequently asked questions

For full details on returns, refunds, eligibility, and timeframes, please refer to our complete Refund Policy here:

👉 Refund and Returns Policy

If you are unsure whether your item qualifies for return, please contact our team before sending anything back and we’ll be happy to help.

Yes — at 100 l/min it's the highest flow rate available from a single-chamber twin-lamp LCD system. Beyond this, our RACK series uses multiple lamps in separate chambers for higher flow.

Yes — it has a free alarm relay contact (NO/NC, 2A max) and a 4-20mA output for tying into a BMS.